<menuitem id="ptjhx"></menuitem>
    Location:Home > Products > DDC building automation system > DDC control system for air handling units
    classification:

    DDC control system for air handling units

    System uses the DDC control to control the air conditioning unit, consisting of air valve, filter, cooler, heater,heating coil fan. The components of the control system is composed of air temperature and humidity transmitter, temperature transmitter, return air temperature and humidity transmitter, antifreeze switch, pressure switch, air valve actuator, electric control valve.

    DDC control system for air handling units

     

    Composition:

    System uses the DDC control to control the air conditioning unit, consisting of air valve, filter, cooler, heater,heating coil fan. The components of the control system is composed of air temperature and humidity transmitter, temperature transmitter, return air temperature and humidity transmitter, antifreeze switch, pressure switch, air valve actuator, electric control valve.

    Monitor and control function:

    The electric air valve, electric control valve and the blower fan interlock, when activated, fresh air valve to open(0-100% can be set), return air valve opening (can be set to 0-100%) electric control valve according to the PID Festival opened; the blower stops, electric, air valve, electric regulating valve is closed at the same time.

    But when the filter is blocked, the pressure switch filter blocking alarm signal is given.

    The winter when the coil temperature is too low, low temperature freezing switch gives a switch signal, the fanstops running, the air valve is closed, the electric control valve to open, in order to prevent the coil. When thefrost preventive switch back to normal, re start the fan, open the air valve, the unit back to work.

    Temperature control air conditioning unit according to the deviation of the most return air temperature and airtemperature, the opening degree of PID by regulating water road, electric control valve, so that the measuredtemperature reaches the set temperature value.

    Humidity control air conditioning unit according to the air humidity and air humidity test set error, opening byPID regulating steam electric valve, so that the measured temperature reaches the set temperature value.

    The fan monitoring and control for the monitoring of fan operation status, fault and hand / automatic control ofair blower, the start and stop.

    This figure of the humidification for dry steam humidizer selection, so the amount of steam electric valve andcontrol humidification, humidification for water, do not use electric regulating valve control device, but directlycontrol humidifier, generally for the state monitoring, control the start and stop.

    組成:
          本空調機組控制系統采用DDC 控 制,由新風閥、初效過濾器、表冷器 加熱盤管、加溫器、送風機組成??刂葡到y的現場元件由新風溫濕度變送器、回風溫度變送器、送風溫濕度變送器、防凍開關、壓差開關、風閥執行器、電動調節閥組成。
    監控與控制功能:
    ※電動風閥、電動調節閥與送風機聯鎖,當送風機啟動時,新風風閥開啟至(0-100%可設定),回風風閥開啟至(0-100%可設定)電動調節閥按P ID 調 節開啟;送風機停止時,電動、風閥、電動調節閥同時關閉。
    ※當過濾器阻塞時,壓差開關給出過濾器堵塞報警信號。
    ※當冬季盤管溫度過低時,低溫防凍開關給出開關信號,風機停止運行,新風閥關閉,電動調節閥打開,以防止盤管凍裂。當防凍開關恢復正常時,重新啟動風機,打開新風閥,機組恢復工作。
    ※空調機組溫度控制為根據回風實測溫度與回風設定溫度的偏差,按PID 調 節水路電動調節閥的開度,使實測溫度達到設定溫度值。
    ※空調機組濕度控制為根據送風實測濕度與送風設定濕度的偏差,按PID 調 節汽路電動調節閥的開度,使實測溫度達到設定溫度值。
    ※送風機的監測與控制為監測送風機的運行狀態,故障狀態和手/ 自 動狀態,控制送風機的啟停。
    ※本圖中的加濕方式為干蒸汽加濕,故選用電動調節閥又控制加濕的蒸汽量,如為水加濕,不選用電動調節閥,而是直接控制加濕器的控制設備,一般為監測其狀態,控制其啟停。

    冷凍站機組DDC控 制

    冷凍站由2 臺 冷水機組、3 臺 冷凍水循環泵、 2 臺 冷卻塔及分集水器等組成??刂葡到y的現場元件為冷凍水供回水溫度傳感器,冷凍水供回水壓差傳感器,冷凍水供水流量計,水流開關,冷卻水供回水溫度傳感器,冷水機組冷凍水電動蝶閥,冷卻水電動蝶閥、冷卻塔冷卻水進口電動蝶閥和壓差旁通閥組成。

    監測與控制功能:

    ※冷水機組的監測:因現有冷水機組基本均帶有以微機處理器為核心的單位控制器, 在 本系統中按單元控制器與樓宇自控系統直接通信
    的 方案, 未 考慮其占用1/0 點 。根據不同情況,也可以采用由冷水機組提供檢測的干節點,控制系統對此進行監測和控制的方案,應根
    據 現場情況確定。
    ※監測冷凍水供回水溫度,以了解冷凍水的工作溫度是否在合理的范圍之內。
    ※監測冷凍水供回水壓差,根據供回水壓差,調節壓差旁通閥的開度。
    ※監測冷凍水供水流量,與冷凍水供回水溫差相結合,可計算出冷量,以此作為能源消耗計量的依據。
    ※監測冷卻水供回水溫度,以了解冷卻水的溫度是否在合理的范圍之內。
    ※冷凍水循環泵,冷卻水循環泵,冷卻塔風機監測與控制點為:運行狀態反饋、故障狀態反饋、手/ 自 動反饋、水泵啟??刂坪妥冾l控制 (反饋數量可根據實際工程需要決定),循環泵與風機可根據現場情況進行啟??刂?。
    ※冷卻塔進水管的電動閥一般采用電動蝶閥,用于當冷卻塔停止運行時切斷水路,以防短路,同時可適當調整進入各冷卻塔的進水量,使 其分配均勻,以保證各冷卻塔都能達到最大使用工況。
    ※冷水機組冷凍側與冷卻側的閥門均采用電動蝶閥, 用 于當冷水機組停止運行時切斷水路,以防水流短路。
    ※群控功能:根據冷凍水供回水溫度與流量,計算出空調系統的實際負荷,將計算結果與當時冷水機組投運臺數下的總供冷量作比較,若 空調系統的實際負荷小于一臺冷水機組的供冷量時,則發出停止一臺冷水機組的運行提示,管理人員確認后停止該機組運行。冷水機組停止運行后,則其相應的冷卻塔、冷凍水泵和冷卻水泵停止運行。

     